TM 5-6115-593-12
TO 35C2-3-463-1
CAUTION
When operating the breaker electrically, do
not disconnect the voltage source until the
motor operator arm has reached the end of
its travel and stopped.
(1)
Disconnect all input bars, bussing,
cables and control circuits to breaker
CB2. The circuit breaker should be
OPEN (OFF) or tripped position. If not,
cycle breaker to OPEN (OFF) by
connecting 120V AC to brown and white
leads.
(2)
Using an ohmmeter, verify that all poles
are open by checking for continuity
between line and load of each pole.
(3)
Verify that all auxiliary switches are
open by checking between each pair
(one red and one white wire in tubing)
and between both yellow wires.
(4)
Connect 24V DC (0.5 amp or greater)
supply to under- voltage trip (blue
leads).
(5)
Cycle breaker to CLOSED (ON) by
connecting 120V AC supply between
yellow and white leads. Wait for motor
operator arm to stop moving before
disconnecting power source.
(6)
Verify that all poles and auxiliary
switches are closed (see steps 2 and 3,
above).
(7)
Trip breaker by removing voltage from
undervoltage trip.
(8)
Check that all poles and auxiliary
switches are open.
(9)
Reconnect
24V
DC
supply
to
undervoltage trip (blue leads).
(10)
Reset breaker to OPEN by connection
120V AC to supply between brown and
white leads. Indicator should point to
OFF (OPEN).
(11) Turn
breaker
ON
(CLOSED)
by
connection 120V AC supply between
yellow and white leads. Indicator
should point to ON.
(12) Verify that all poles are closed.
(13) Turn
breaker
OFF
(OPEN)
by
connecting 120V AC supply between
brown and white leads. Indicator
should point to OFF.
(14) Verify that all poles are open.
(15) Disconnect all voltage supplies.
(16) Refer to next higher maintenance for
repair if necessary.
d. Installation.
(1)
Install circuit breaker CB2 (44, figure 4-
12) using eight screws (43). Connect
buss bars (40, 41 and 42) using bolts
(37) and screws (35), washers (36 and
38) and nuts (39).
NOTE
Indicator on cover shows position of
operator arm and not motor operator drive,
except when sequence is proper.
CAUTION
Manual operation of circuit breaker CB2
can be achieved by removing operator arm
retaining device, removing operator arm,
and installing arm onto indicator hub nut. If
arm is to be manually operated from OFF
to
ON
(OPEN
to
CLOSED),
the
undervoltage trip (blue leads) must be
energized.
(2)
Refer to figure 4-15 and manually
restore electrical sequence by removing
operator arm retaining device and
removing operator arm, then install arm
onto indicator hub nut and connect a
24V DC (0.5 amp or greater) power
supply to the undervoltage tro[ (blue
leads). Manually operate the breaker
by moving the operator arm.
4-47