TM 5-6115-593-12
TO 35C2-3-463-1
(2)
Plug test set-up into 120V AC power
supply.
(3)
Observe that neither of the 120V AC test
lamps light.
(4)
Depress and hold pushbutton A; lamp A
should light and lamp B should remain
extinguished.
(5)
Release pushbutton A and depress and
hold
pushbutton
B;
lamp
A
should
extinguish and lamp B should light.
(6)
Depress and hold pushbutton A and then
also depress and hold pushbutton B; note
that transfer does not take place.
(7) Wire contactor K109 into test set-up as
shown in figure 4-14.
(8)
Plug test set-up into 120V AC power
supply.
(9)
Observe that test lamp does not light.
(10)
Depress and hold pushbutton; test lamp
should light.
(11)
Release pushbutton; test lamp should
extinguish.
(12)
Refer to next higher maintenance for
repair of any defective contactors.
c.
Replacement. Replace defective contactors as
follows:
(1)
Remove contactors K107 and K109 (54)
by disconnecting and tagging lead wires,
and removing screws (52) and washers
(53).
(2)
Remove
contactor
K108
(51)
by
disconnecting and tagging lead wires, and
removing screws (49) and washers (50).
(3)
Install contactors K107 and K109 (54)
using screws (52) and washers (53) to
secure contactors side wall of external
power enclosure (94). Connect wires and
remove tags.
(4)
Install contactor K108 (51) using screws
(49) and washers (50) to mount contactor.
Connect wires and remove tags.
4-24. MAIN CIRCUIT BREAKER CB2.
a.
Inspect. Inspect main circuit breaker CB2 (44,
figure 4-12) for loose or broken wires and
damaged case.
b.
Removal. Remove circuit breaker CB2 (44,
figure 4-12) as follows:
WARNING
Set MAINTENANCE LOCKOUT switch
to
MAINTENANCE
LOCKOUT.
Disconnect
negative
cable
from
batteries. Remove external power by
opening CB101 and disconnecting.
Load terminals of generator set circuit
breaker (CB2) may still be energized
with the bus voltage. (1) Disconnect
input bars from reconnection panel to
CB2.
(2)
Disconnect buss bars (40, 41, and 42) by
removing bolts (37) and screws (35),
washers (38) and nuts (39).
(3)
Free upper set of circuit breaker buss bars
by removing fastening hardware.
(4)
Remove circuit breaker CB2 (44) from
enclosure (99) by removing eight screws
(38).
c.
Test. Refer to figures 4-14 and 4-15 and
proceed as follows:
WARNING
Disconnect all input bars, bussing,
cables and control circuits to breaker
before starting test procedure.
NOTES
1.
Manual operation of circuit breaker disorders the
sequence of electrical control, Do not attempt to
operate the breaker from OPEN (OFF) to
CLOSED
(ON)
without
energizing
the
undervoltage trip. To restore electrical mode of
operation, the breaker must be cycled into
CLOSED (ON) or OPEN (OFF) position as
indicated
on
motor
cover.
4-44