TM5-6115-585-34NAVFACP-8-623-34TO-35C2-3-455-2TM-05684C/05685B-34Table 9-1. Test ScheduleTestInstrumentc. Test Procedure.Test Method (MIL-STD-705)513. 1CRecord only the readings of the masterand panel instruments at no-load, 50’%and 100% of rated load. Record thereadings of the master and panel in-struments at all voltage connections.(1) Position switches as follows:(a) Master switch-stop.(b) Panel light switch-off.(c) S1-closed.RequirementsAccuracy shall be as follows:Current indicator system, 10% max.Voltage indicator system - Initialaccuracy 2. 5% of full scale except thatwithin the ranges of 115 to 125 and 200to 250V. The error shall not exceed 3and 5 volts respectively.Frequency indicator system 0.5%maximum.Voltage adjust range shall be between197.6 and 218. 4V for the 120/208V, 3phase 4 wire connection between 114and 125V for the 120V, 1 phase, 2 wireconnection between 228 and 252V forthe 120/240V, 1 phase, 3 wire connec-tion.Figure 9-1. Adjusting R3 ResistorFigure 9-2. Testing Engine Control Circuitry9-2
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business