load equals a 100% meter reading for maximum ratedload. A 1.0 power factor load equals a 80%. meterreading for maximum rated load.i. During operating of the Generator Set observethe following.(1) Check 9. rated current meter.(2) Check fuel level gage periodically.(3) Oil pressure gage located on engine should in-dicate 20 psi minimum.TM 5-6115-585-12NAVFAC P-8-623-12TO-35C2-3-455-1TM-05684C/05685B-12(5) Battery indicator should indicate yellowwhile battery is charging, green when battery is fullycharged.(6) AC voltmeter should indicate 120V., 208V. or240V. depending on load connection.( 7 ) F r e q u e n c y m e t e r s h o u l d i n d i c a t e 6 0 Hz(MEP-003A) or 400 Hz (MEP-112A) at rated load.j. During operation, inspect for leaks, paying par-ticular attention to engine fuel and oil lines andconnections.(4) Check running time meter periodically inorder to perform preventive maintenance check-andservices at proper intervals.Figure 2-4. Load Terminal and Reconnection Configuration2 - 5C h a n g e 2