TM 5-6115-585-12
NAVFAC P-8-623-12
TO-35C2-3-455-1
TM-05684C/05685B-12
Figure 2-3.
Control Panel
increase frequency, pushing speed control knob in will
decrease frequency. For fine control turn knob CW to
increase and CCW to decrease.
f. Place ammeter-voltmeter transfer switch in
position corresponding to the position of the reconnec-
tion switch. Adjust voltage adjust rheostat to desired
voltage as read on voltmeter. Turn rheostat clockwise
to increase voltage or counterclockwise to decrease
voltage.
g. Place AC circuit breaker in ON position. Adjust
speed control to obtain full load frequency per
paragraph 1-10.b.
h . P l a c e a m m e t e r - v o l t m e t e r t r a n s f e r s w i t c h in
position to check percent rated current for either
1-phase 120 V. output, l-phase 120/240 V. output, or
3-phase 120/208 V. O Utput. See table 2-1 and figure
2-3.
N O TE
For 3-phase output each of the four posi-
t i o n s i n d i c a t e d i n t a b l e 2 - 2 m u s t be
checked.
Observe percent rated current meter. Do not exceed
5% load difference between phases. A 0.8 power factor
Table 2-2. Reconnection Switch Positions
2-4
Change 2