4-25.T M 5 - 6 1 1 5 - 5 8 5 - 12N A V F A C P - 8 - 6 2 3 - 12T O – 3 5 C 2 – 3 - 4 5 5 -1T M - 0 5 6 8 4 C / 0 5 6 8 5 B - 1 2Figure 4–15. Fuel Solenoid Test Set–Up.Section X. MAINTENANCE OF ENGINE ELECTRICAL SYSTEM4–24. DESCRIPTION AND FUNCTION.a. The engine is cranked by a 24 volt electricstarting motor (see figure 1–7). When starting motorsolenoid is energized, the solenoid core pulls in, shift-ing the pinion gear into engagement with the engineflywheel ring gear. At the same time, contacts in thesolenoid close to provide a circuit for the starter. Thestarting motor is protected from overspeeding by anoverrunning clutch. Two 12 volt batteries in series areused. The starting switch for this starting circuit is lo-cated in the control cubicle, A blower wheel alternatoris utilized to maintain the battery charge. The stator ismounted on the engine block and the permanent mag-net rotor is mounted into the air cooling system blower.Solid state diode rectifiers convert the alternating cur-rent generated in the stator to direct current for batterycharging.b. A new (Style II) gear–reduction electric starterwill be installed on engines manufactured during 1990;and will be available as a replacement when the origi-nal starter, (Style I ) is no longer available. The Style IIstarters are interchangeable with the Style I starter.c. Slave receptacle is used to supply externalcranking power and as an output receptacle for otherequipment. Refer to Figure 4–34 for removal and in-stallation of slave receptacle.Metal objects making contact be-tween the positive and negativebattery terminals, or between thepositive battery terminal and the gen-erator frame can cause FIRE orEXPLOSION,Always keep the bat-tery terminal covers on the batteryterminals. See Figure 3–2,BATTERYASSEMBLY.Battery Cables (Including Jumper Cable). OnASK equipped generators, remove BATTERIES ac-cess door.(1) Test. Test battery cable for continuity, Re-place any cable that does not show continuity,(2) Remove. Remove negative battery cablefrom negative (–) battery terminal. Remove positive(+) battery cable from positive battery terminal.Tag and disconnect cables from starter case andstarter solenoid. Remove jumper between batteries.Clean battery, starter, and starter solenoid terminalsthoroughly and install new cables as given below.(3) Replace. Attach jumper cable betweennegative (–) terminal of one battery and positive (+) ter-minal of the other battery. Attach positive battery cableto the “B” Terminal stud on starter solenoid. Attach4–24Change 11
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business