TM5-6115-585-12
NAVFAC P-8-262-12
TO-35C2-3-455-1
TM-05684C-12
Figure 4-7. Fuel Tank Assembly
(4) Fuel Level Gauge. Engage threads of fuel
(3) Check that drain valve is closed before filling
level gauge (5) 1/2 turn into tank (9). Coat threads
with sealing compound MIL-S-22473. Tighten float
level gauge into tank using tools only on hex portion
of gauge. Install filler cap (4) and strainer (5) into tank
(9).
g. Installation.
(1) Install straps (3) onto the skid-base and se-
cure with nut (1) and flatwasher (2) on inside of skid-
base only.
(2) Position fuel tank assembly onto skid-base, position
straps over tank assembly and secure with nut (1) and flat-
washer (2). On ASK equipped generators, install side
closure, left panel and top panel assemblies (para. 5-4 and
5-5).
tank with proper grade of fuel.
NOTE
After each time fuel filters or strainer is
drained or elements replaced, purge air from
fuel system by moving master switch on con-
trol panel to PRIME & RUN position. This
should activate the fuel transfer pump and
force trapped air back to the vented fuel tank.
4-20. FUEL FILTER ASSEMBLIES AND STRAINER
ASSEMBLY.
There are two identical fuel filter assemblies (see
figure 3-13), one which acts as the primary and the
4-17
Change 8