TM5-6115-584-34NAVFAC P-8-622-34TO-35C2-456-2(2) Testing Armature.(a) Testing Armature for grounds. Toucharmature shaft and the end of each commutator barwith a pair of ohmmeter leads. There should be nocontinuity. If continuity is indicatd betweenany commutator bar and armature shaft, it indica-tes a grounded armature. Replace grounded arma-ture. See figure 5-4.(b) Testing Armature for shorted Coils.A growler is necessary to test for shorted coils.With the armature in the growler, turn thegrowler on and hold a thin steel strip parrallelover the armature surface. Turn qrowler on, andif the steel strip vibrates or is attracted to thearmature surface, the armature is shorted orgrounded.Turn off growler, rotate armature one-quarter turn and repeat test. Do this for onecomplete revolution of armature. See figure 5-5.If armature has a short or is grounded, replaceit.(c) Testing Armature for Open Coils.Test coils for continuity with ohmmeter. Place onelead on commutator bar, other lead on the next bar.If there is discontinuity (infinite resistance),Figure 5-4. Testing Armature for GroundsFigure 5-5. Testing Armature for Shorted CoilsFigure 5-6 Testing Armature for Open Coilsthe reading indicates open coil. See figureIf armature has an open coil, replace it.5-6.C h a n g e 75 - 5