Figure 1-6. Operating Instruction Plate
Figure 1-8. Voltage Reconnection Instruction Plate
TM-5-6115-545-12 Power Unit Utility Pack Gas Turbine Engine Driven (Air Research Model PPU85-5) Non-Winterized and (Air Research Model PPU85-4) Winterized Manual
Page Navigation
4
5
6
7
8
9
10
11
12
13
14
Figure 1-7. Service Instructions and System Capacities Instruction Plate
b
.
Tabulated
Data
.
(Cont)
Switch contact data
Normal fuel level is 2.00±0.12 inches from top of tank.
Open
continuity
exists between connector pins A-B (upper
switch) and C-D (lower switch).
When fuel level drops below 2.75±0.12 inches from top of tank-
Upper switch is closed and lower switch opens.
When fuel level drops below 5.75
±
0.12 inches from top of tank-
Upper and lower switches are closed.
(6)
Engine
accessories
.
(a)
Fuel
transfer
pumps
.
Model (MS) . . . . . . . . . . . . . . . MS5132-2
Volts . . . . . . . . . . . . . . . . . . . . .24dc
psi(max) . . . . . . . . . . . . . . . . . .7
Delivery (max) . . . . . . . . . . . . .18 gallons per hr