TM 5-6115-465-34
TO 35C2-3-446-2
NAVFAC P-8-625-34
TM 06858B/06859D-34
Table 7-1.
OPERATING TESTS
MIL-STD-705
PROCEDURE
TEST
TEST PARAMETER
Regulator and governor stability and
608.1a
See tables 7-2 and 7-3.
1.
transient response. (Short Term).
Overspeed protection device.
2.
505.2a
2400 rpm to 2450 rpm.
Phase balance.
3.
508. 1C
See tables 7-2 and 7-3.
Circuit interrupter (Short Circuit).
4.
512.lc
Instantaneously at 425
25 percent of rated
current.
8 2 minutes at 130
Circuit interrupter (Overload Trip).
5.
512.2c
percent of rated
current.
Circuit interrupter (Undervoltage).
6.
512.3c
Instantaneously below
(Class 1 sets only).
48 volts, 6 2 seconds
at 99 + 24 volts or less.
Circuit interrupter (Overvoltage).
7.
Not more than 1 second
512.3c
after voltage has risen
to and remained at any
value greater than 153
3 volts for not less
than 200 milliseconds.
8.
514.1
60 Hz = 55 1
Trip).
50 Hz = 46 1
400 Hz = 370 5
9.
Low oil pressure protective device.
515.la
Trip pressure 17 + 3 psi.
Reverse power protective device.
10.
High coolant temperature protective.
11.
515.2a
Trip temperature 222
3F.
12.
Low fuel protective device.
13.
Regulator range.
511.lc
Test at both 50 Hz and
60 Hz for Mode I sets.
See tables 7-2 and 7-3.
Phase sequence (Rotation).
14.
507.lc
Ll, L2, L3.
15.
511.2b
See tables 7-2 and 7-3.
Parallel operation provisions.
16.
17.
Malfunction indicator system.
Maximum power.
18.
640.4
a.
30kW, 50/60 Hz, TU and TP 42.2kW
b.
30kW, 400 Hz, TU 24.2 kW
CAUTION
Prior to performing any of the operating tests listed in table 7-1, insure that
the generator set is serviced with the correct fuel, oil, and coolant as listed
on the data plate.
7-3