TM 5-6115-465-34
TO 35C2-S-446-2
NAVFAC P-8-625-34
TM 06858B/06859D-34
Figure 5-9.
b. = Cleaning, Inspection, and Testing.
follows:
clean, - lint-free cloth moistened with an approved
between terminal Al and A2, B1 and B2, Cl and
solvent and dry thoroughly.
each case.
(2) Inspect transformer assemblies for
(b) Apply 10V-60 Hz to secondary winding.
cracks, corroded terminals, and evidence of short-
Exaltation current shall be 0.050 amp (maximum).
ing.
(5) Test cross-current compensation trans-
(3) Test current boost transformer as follows:
former as follows:
(a) Using a ohmmeter, check resistance
between terminals Al and A2, B1 and B2, and Cl and
(b) Apply 10V-60 Hz to secondary winding.
each case.
Excitation current shall be 0.050 amp (maximum).
(6) Replace defective or damaged transformers.
(b) Apply 7V-60 Hz to secondary winding.
Excitation current shall be 0.075 amp (maximum).
c. Installation. Install transformer assemblies
in reverse order of removal procedures.
5-15