(2) Cleaning and Inspection.
h.
Kilowatt Meter.
(a) Clean AC current meter with filtered
(1) Removal.
compressed air or wipe with a clean, lint-free cloth
lightly moistened with an approved solvent.
(a) Tag and discomect electrical leads to
kilowatt meter.
(b) Visually inspect AC current meter
for corrosion, cracked casing, cracked or broken
(b) Remove self-locking nuts (25, figure
glass, stripped or otherwise damaged threads and
3-37, sheet 1 of 3)
and screws (26).
evidence of shorting or other damage.
(c) Remove kilowatt meter (27) from
(3) Installation. Install AC current meter in
panel.
reverse order of removal procedures.
(2) Cleaning andhspection.
(a) Clean kilowatt meter with filtered
k. AC Voltmeter.
compressed air or wipe with a clean, lint-free
cloth lightly moistened with an approved solvent.
(1) Removal.
(a) Tag and disconnect electrical leads to
(b) Visually inspect kilowatt meter for
corrosion, cracked casing, cracked or broken
glass, stripped m damaged threads, and evidence
(b) Remove self-locking nuts (35, figure
of shorting or other damage.
3-37, sheet 1 of 3)
and screws (36) to
remove AC
(3) Installation. Install kilowatt meter in
reverse order of removal procedures.
(2) Cleaning and Inspection.
i. Thermal Watt Converter.
(a) Clean AC voltmeter with filtered com-
pressed air or wipe with a clean, lint-free cloth
(1) Removal.
light ly moistened with an approved solvent.
(a) Tag and disconnect electrical leads
(b) Visually inspect AC voltmeter for
to thermal watt converter.
corrosion, cracked casing, cracked or broken glass,
(b) Remove self-locking nuts (28, figure
stripped or otherwise damaged threads, and evidence
3-37, sheet 1 of
3), screws (29) and washers (30) to
of shorting or other damage.
remove thermal watt converter (31) from control
(3) Testing. If an AC voltmeter is suspected
cubicle assembly.
of being faulty, test by temporarily replacing with
another which is known to be serviceable. If the in-
(2) Cleaning and Inspection.
correct reading persists, the original meter is ser-
viceable and should be reinstalled.
(a) Clean thermal watt converter with
filtered compressed air or wipe with a clean, lint-
(4) Installation. Install AC voltmeter in re-
free cloth lightly moistened with an approved sol-
verse order of removal procedures.
vent.
l.
Volts-Amps Transfer Switch.
(b) Visually inspect thermal watt con-
vert er for dents, cracks, corrosion, stripped or
(1) Removal.
otherwise damaged threads, and evidence of short-
ing or other damage.
(a) Tag and disconnect electrical leads to
volts-amps transfer switch.
(3) Installation. Install thermal watt con-
verter in reverse order of removal procedures.
(b) Loosen setscrews in control knob (38.
AC Current Meter.
j.
(c) Remove nut (39) to remove switch
(1) Removal.
(40) from panel.
(a) Tag and discomect electrical leads to
(2) Cleaning and Inspection.
AC current meter.
(a) Clean volts-amps transfer switch wtth
(b) Remove self-locking nuts (32, figure
filtered compressed air or wipe with a clean, lint-
3-37, sheet 1 of 3)
and screws (33) to
remove AC
free cloth lightly moistened with an approved solvent.
current meter (34) from panel.
3-74