Continous
Duty Cycle
0.75 amperes at 32 VDC after 30
Maximum Holding Current
minutes warmup.
Pulling Current
Contactor shall close with 24 VDC applied
across the operating coil and a 5.0 ohm
resistor in series.
Electrical Life
10,000 cycles at a duty cycle of not less than 325
make and break operations per hour. With the ON
portion of the cycle not less than 1.0 seconds and
the OFF portion of the cycle not more than
10.0 seconds.
Mechanical Life
100,000 cycles
Weight
4 pounds (approx.)
4.80 x 6.06 x 4.80 inches (approx.)
Overall dimensions
4A. Circuit Breaker Assembly (CB2) (400 hertz generator sets)
76-4191
DOD Drawing Number
Consolidated Diesel Electric Co.
Manufacturer
Old Greenwich, Connecticut
3 pole normally open, 400 ampere
Main Contacts
350 amperes continuous at 208 volts and
Current Rating (minimum)
175 amperes at 416 volts
1600 amperes for 4 seconds
42,000 amperes
Interrupting Capability
30,000 amperes at 416 volts
SPST normally open contacts,
Auxiliary Contacts
3 rated 10 amperes; 1 rated 5 amperes
-65F to +135 F
Temperature Range
25 pounds (approx.)
Weight
7.75 x 8.50 x 16.00 inches (approx.)
Overall Dimensions