KVA Rating
125 KVA
Mechanism
Electrically held
3 PST double break
Main Contacts
AC Voltage
120/208-240/416 Volts
50/60 and 400 Hertz
50/60 and 400 Hertz
Continuous Current
350 amperes at 120/208
volts
50/60 and 400 hertz
750 amperes at 120/208
volts
Second Current
50/60 and 400 hertz
5000 amperes at 120/208
volts
Interrupting Capacity
50/60 and 400 hertz
2500 amperes at 240/416
volts
50/60 and 400 hertz
4 SPST normally open, 2 SPST normally closed
Auxiliary Contacts
and 1 SPDT.
32 Volts
DC Voltage
2.5 amperes maximum resistive or
Current
inductive
120 Volts
AC Voltage
2.0 amperes maximum
Current
Lamp Current
4.0 amperes maximum
DC
1.5 amperes maximum
50/60 Hertz
3.0 amperes maximum
400 Hertz
Within 0.004 seconds of main contacts
Auxiliary Contacts Trip
activation.
Time
Coil Data
32 VDC Maximum
Operating Voltage
16 VDC Minimum (without external series
resistance)
Main Contacts Maximum
Operating Time
0.050 Seconds at 24 to 32 VDC with 0.25 ohms
Close
0.035 Seconds at 24 to 32 VDC with 0.25 ohms
Open