• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
CIRCUIT INTERRUPTER TEST (OVER VOLTAGE AND UNDER VOLTAGE).
LOW OIL PRESSURE PROTECTIVE DEVICE TEST - TM-9-6115-464-34_398

TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
  371    372    373    374    375  376  377    378    379    380    381  
ARMY TM 9-6115-464-34 AIR FORCE TO 35C2-3-445-2 NAVY  NAVFAC  P-8-624-34 (f)  Read  and  record  both  voltmeter  readings. (g)  With the oscillograph recording and the circuit interrupter closed, close the switch. (See figure 512.3-I. (h)  Reactivate the shutdown provision if used. (i)   The   generator   set   contains   an   ovewoltage   malfunction   indicator;   check   and   record   its   indication. (j)  Record whether or not the set shuts down. (k)  Open the switch, reset the ovewoltage circuit if necessary, restart the set if required, and close the circuit interrupter. (1) Repeat steps (e) thru (k) above two additional times. d.  Procedure  II  (Undervoltage). (1)   Preparation   for   test. (a)  Locate the input terminals of the undervoltage sensing circuit and connect the apparatus as illustrated in figure 512.3–I. (b)  Repeat step (b) of para. 4-20c. (1) (b). (2)   Test. (a) (b) (c) (d) (e) (f) (9) (h) (i) Start and operate the set at rated frequency and no load. Close the switch (see figure 512.3–I) and use the resistance, R1, to adjust the voltage to the rated value. Open the switch and adjust the resistance, R2, until Voltmeter No. 2 reads the undervoltage value specified in table 4-1. This test shall be repeated for each undervoltage value. Repeat steps (b) and (c) above to assure that the specified undervoltage and rated voltage settings are  correct. Set the oscillograph chart speed such that the individual waveform peaks are clearly visible. Set the timing lines to a minimum of 0.01 seconds per line or use a 60 Hertz timing trace. With the switch open, adjust the trace peak–to-peak amplitude to a minimum of one inch (or 25 millimeters). With the set operating and the circuit interrupter and the switch open, read and record both voltmeter readings. Close the switch and circuit interrupter. With the oscillograph recording, open the switch. After allowing sufficient time for the circuit interrupter to operate, check and record the indication of the undervoltage malfunction indicator. (j) Close the switch and close the circuit interrupter. (k) Repeat steps (e) thru (j) above two additional times. (l) Repeat (a) thru (k) for the other undervoltage value specified in para. 4-1. 4-20







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.