• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
For Class II Sets
CHAPTER 5 FOR MATERIAL USED IN CONJUNCTION WITH THE GENERATOR SET

TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
  376    377    378    379    380  381  382    383    384    385    386  
ARMY TM 9-6115-464-34 AIR FORCE TO 35C2-445-2 NAVY  NAVFAC  P-8-624-34 (e)   Results. 1. Average the three valid power readings. This average is the observed maximum power value. 2. Correct the observed maximum power value to standard conditions using the procedure in MIL–HDBK-705, Method 220.2, paragraph 220.2.3. This is the corrected maximum power value. 3.    Compare these results with the requirements of table 4-1. 4-24.  UNDER  FREQUENCY  PROTECTIVE  DEVICE  TEST a.   General. For generators that power certain types of equipment, it is extremely important that the circuit interrupter open when the frequency fails appreciably below rated value. Severe damage may otherwise result to the powered equipment. To insure that the circuit interrupter will open at or before the critical frequency value, the generators are equipped with an underfrequency protective device. The device on this generator operates electrically. Although the under frequency protective device must be capable of functioning at any voltage throughout the specified voltage operating range, it is necessary only to perform the test at the specified maximum, at rated, and at minimum voltage limits. b. Apparatus   Instrumentation for measuring load conditions shall be as described and illustrated in method 205.1. paragraph 205.1.10 of MILL-HDBK-7050. c. Procedure. (1) Preparation for test. Connect a voltmeter and frequency meter to the generator set terminals, ahead of the circuit interrupter, and the remainder of the apparatus as shown in the applicable figure of paragraph  205.1.10  of  MIL-HDBK-705. (2)   Test. (a)  Operate the generator at rated speed and voltage, and at no load since the generator is equipped with an electrical-type underfrequency protective device, this test shall be repeated with the voltage adjusted to maximum and minimum voltage for the specified voltage operating range. (b)  With the circuit interrupter closed, slowly decrease the operating speed until the protective device causes the circuit interrupter to open. The electric governor must be deactivated to sufficiently decrease the speed on Class 1, precise sets. (c)  Record the speed. (d)  Repeat the test while rapidly decreasing the operating speed. Again record the speed. (e)  Operate the generator at rated speed and voltage, and at rated load. (f)  Repeat steps (b), (c) and (d). d. Results. Compare the test value of frequency with that given in table 4-1. 4-25/(4-26 blank)







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.