TM 9-6115-668-135.9 POWER SUPPLY NT2 24 V MAINTENANCE.This task covers:a. Removalb. InstallationEquipment ConditionsGeneral Mechanic’s Tool KitReference(item 2, appendix B)Generator Set 150 kW shutAutomotive Fuel and Electrical System Repair, Tool Kitdown,(item 3, appendix B)paragraph 2.5.2WARNINGDisconnect the negative battery cable first and then the positive bat-tery terminal cables. Failure to observe this warning could result In se-vere personal injury or death.C A U T I O NTag all cables prior to removal to ensure correct connection of the cablesduring Installation.REMOVAL1.Open flap (2, figure 5-23) on unit hood assembly (1).2.Open front panel (2) and secure with prop (5).N O T ERemoval procedure for all power supply components NT2 24 V isthe same as for time relay K26, described below.3.Remove time relay K26 (19) as instructed in paragraph 5.8.4.Push the closures on power supply component (16) apart in direction of arrow, and pull power sup-ply component (16) out of time relay K26 (19).NOTEInstallation procedure for all power supply components NT2 24 Vis the same as for time relay K26, described below.1.Insert power supply component (16) in timing relay K26 (19).2.Install timing relay K26 (19) as instructed in paragraph 5.8.3.Stow prop (5) and close front panel (4).4. Close flap (2).5-108