5.
Set time relay (Wipe Relay) K17 (23) to switching time of 0.5 seconds:
a. Insert jumper Y1-Y2 into lower row of terminal as shown in figure 5-21.
Figure 5-21 Time Relay k17
6.
Set time relay K25 (44) to switching time t1 = 0.5 seconds and pulse time t2 = 0.5 seconds:
a. Insert jumper Y1 -Y2-Y3 (1) into upper row of terminal as shown in figure 5-22.
b. Set switching time t1:
On front of time relay K25 (44), use TIME DIP switches (2) to set a 1 -seconds time
window as indicated in figure 5-22.
On front of time relay K25 (44), use rotary knob (4) to set a multiplication factor of .5.
c. Set pulse time t2:
On front of time relay K25 (44), use TIME DIP switches (5) to set a 1 -seconds time
window as indicated in figure 5-22.
On front of time relay K25 (44), use knob (6) to set a multiplication factor of .5.
5-106