paragraph 4.44TM 9-6115-666-13 DANGEROUS VOLTAGE EXISTS ON LIVE CIRCUITS. AL- WAYS OBSERVE SAFETY PRECAUTIONS AND NEVER WORK ALONE. FAILURE TO OBSERVE THIS WARNING COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH. NO I Measure voltage at I YES - K7114and K7lA.2: - 24 VDC? v Replace K7 (PARAGRAPH 5.7) NO v Measure voltage at S4/1 and K7lA2: 24 VDC? YES Repair or Replace NO Measure voltage at S4/2 and K7lA2: 24 VDC? h YES v Repair or Replace cables “4 1” and “0” NO Measure voltage at K7/44 and K5lA2: 24 VDC? YES Replace K7 (PARAGRAPH 5.7) ‘I Continue on Page 6 Figure 5-15 UNDER/OVER FREQUENCYlamp lights up during operation (sheet 5 of 6). 5-79