TM 9-6115-668-134.39 FUEL LINES AND TWO STEP FUEL FILTER ASSEMBLY MAINTENANCE.This task covers:a. Removalb. ServiceC.InstallationINITIALSETUPMaterials/PartsEquipmentConditionsSealing ringsReferenceGenerator Set 150 kW shutdown, paragraph 2.5.2REMOVAL1.Open flap (1, figure 4-41)CAUTIONPlace collection container under two step fuel filter assembly.2.Remove bleed screws (6, 7) and sealing rings from two step fuel filter assembly (8) and drain fuelinto container. Discard sealing rings.SERVICE1.Unscrew handle (4) by turning to the left.2.Install bleed screws (6, 7) with new sealing ring three turns into fuel filter assembly (8).3.Pull and push handle (4) of priming pump (5) until fuel emerging from hole in screw threads of bleedscrews (6, 7) contains no bubbles and tighten bleed screws (6, 7).INSTALLATION1.Remove collection container under two step fuel filter assembly.2. Close Flap (1).4 - 9 2
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business