TM 9-6115-668-134.5 INSTALLATION INSTRUCTIONS.Refer to paragraph 2.3.54.6 PRELIMINARY SERVICING AND ADJUSTMENT OF EQUIPMENT.CAUTIONAt temperatures below 32° F (0 ° C), if the batteries are not fully chargedthey will be damaged or destroyed.4.6.1 Batteries.The batteries in the battery set assembly are maintenance free.No electrolyte can leak out during proper operation; there is no need to top up with distilled water;The batteries exhibit very little self-discharge, so there is no need for frequent recharging to makeup for self-discharge losses.4.6.2 Fuel Tank.Fill fuel tank (paragraph 2.3.4) with fuel type in accordance with table 4-1. Fuel tank capacity is 101.7 gal-ions (385 liters).Table 4-1 FuelAMBIENT TEMPERATUREDIESEL FUEL+20 °F TO +120 °F (-6 °C TO 49 °C)W-F-800 GRADE DF-2, JP4, JP5, OR JP80 °F TO +20 °F (-17 °C TO -6 °C)W-F-800 GRADE DF-1, JP4, JP5, OR JP8-25 °F TO 0 °F (-32 °C TO -17 °C)W-F-800 GRADE DF-1-25 °F TO 0 °F (-32 °C TO -17 °C)W-F-800 GRADE DF-A4-12