TM 9-6115-668-13
2.7 PREPARATION FOR MOVEMENT.
2.7.1
Shut Down Generator Set 150 kW,
Refer to paragraph 25.2
2.7.2 Disconnecting Control Power Cables.
WARNING
Potential 205 VAC shock hazard. Do not disconnect or connect control or power cables while
Generator Set 1 or 2 is running.
Always install protective covers on control and power cables when cables are disconnected.
Failure to observe this warning could result in severe personal injury or death by electrocution.
a. Disconnect control cable as follows:
(1)
Unscrew control cable (2, figure 2-21) and pull out of J9 PARALLEL OPERATION receptacle.
(2)
Place protective cap (1) on control cable connector.
(3)
Place protective cap (3) on J9 PARALLEL OPERATION receptacle.
b.
Disconnect power cable as follows:
(1)
Unscrew connector (4, figure 2-21) and pull power cable L1 out of receptacle L1 (ØA).
(2)
Place protective cover (8) on cable connector.
(3)
Unscrew connector (5) and pull power cable L2 out of receptacle L2 (ØB).
(4)
Place protective cover (9) on cable connector.
(5)
Unscrew connector (6) and pull power cable L3 out of receptacle L3 (ØC).
(6)
Place protective cover (10) on cable connector.
(7)
Unscrew connector (7) and pull power cable N out of receptacle N.
(8)
Place protective cover (11) on cable connector.
2.7.3 Disconnect Battery Cable.
a. Disconnect battery cable as follows:
(1)
Pull battery cable (1, figure 2-22) out of SLAVE RECEPTACLE 24 VOLTS on each Generator Set 150 kW.
(2)
Place protective cap (2) on J3 SLAVE RECEPTACLE 24 VOLTS.
2.7.4 Disconnect Ground Cable.
a. Disconnect ground cable as follows:
(1) Remove nut (1, figure 2-23), serrated washer (2) washer (3), and detach ground cable (4) and washer (5)
from connector bolt (6).
(2)
Install washers (2,3 and 5) and nut (1) onto bolt (6) and tighten nut (1).
2-60 Change 1