TM 9-6115-668-132.5.2 Generator Set 150 kW Shutdown.Open Flap (1, figure 2-19).2.5.2.1 Normal Shutdown.a.Press AC CIRCUIT INTERRUPTER OFF pushbutton switch (3):Lamp in AC CIRCUIT INTERRUPTER ON illuminated pushbutton switch (2) goes out.CAUTIONBefore shutting down Generator Set 150 kW, allow It to operate for fiveminutes with no load applied.b.Turn MASTER SWITCH to OFF (4). Pull key ¼ to ½ way out from MASTER SWITCH.c.Perform the Preventive Maintenance Checks and Services (PMCS) listed as “AFTER” in table 2-4.Figure 2-19 Generator Set 150 kW Shutdown.2-57