TM 9-6115-662-13&P
POWER PLANT OPERATING PROCEDURES
BEFORE OPERATION
1. CHECK/SERVICE BOTH GEN SETS BEFORE OPERATION. CONNECT "GND" TERMINAL TO GROUND.
CONNECT CONTACTOR POWER CABLE.
INDICATOR LIGHTS
1. STATUS LIGHT, INDICATES LINE BETWEEN GEN AND SW BOX IS HOT.
2. ON LINE LIGHT, INDICATES SWITCH BOX CONTACTOR IS CLOSED FOR INDICATED GEN.
OPERATING PROCEDURES
1. START EITHER GEN. ADJUST VOLTAGE AND FREQUENCY.
2. PUT GEN CKT INTRPT SWITCH IN CLOSED POSITION. (SWITCH BOX STATUS LIGHT SHOULD LIGHT.)
3. AT SWITCH BOX, SET ON-OFF SWITCH TO ON. (ON LINE LIGHT SHOULD LIGHT.)
LOAD TRANSFER PROCEDURES (SETS CONNECTED FOR PARALLEL OPERATION PER TM)
1. ON OPERATING GEN, (GEN NO. 1) SET UNIT-PARALLEL SWITCH TO PARALLEL.
2. START GEN NO. 2. ADJUST VOLTAGE AND FREQUENCY TO MATCH GEN NO. 1.
3. AT SW BOX, SET GEN NO. 2 ON-OFF SWITCH TO ON. (ON LINE AND STATUS LIGHTS SHOULD LIGHT.)
4. AT GEN NO. 2, SET UNIT-PARALLEL SWITCH TO PARALLEL. BOTH SYNCHRONIZING LIGHTS SHOULD
BE GOING BRIGHT TO DARK TOGETHER.
5. INCREASE FREQUENCY UNTIL SYNCHRONIZING LIGHTS BLINK TOGETHER ONE OR MORE TIMES PER SECOND.
6. DECREASE FREQUENCY UNTIL LIGHTS BLINK TOGETHER ONCE EVERY 3-4 SECONDS.
7. WHEN LIGHTS ARE DARK, SET GEN NO. 2 CKT INTRPT SWITCH TO CLOSE. GEN CONTACTOR LIGHT
SHOULD LIGHT AND SYNCHRONIZING LIGHTS SHOULD GO OUT.
8. AT GEN NO. 1, SET CKT INTRPT SWITCH TO OPEN, SET UNIT-PARALLEL SWITCH TO UNIT.
TURN MASTER SWITCH TO STOP. (AT SWITCH BOX, ON LINE AND STATUS LIGHTS FOR GEN NO. 1
SHOULD GO OFF.)
9. AT GEN NO. 2, SET UNIT-PARALLEL SWITCH TO UNIT.
Figure 2-14. Power Plant Instruction Plate.
2 - 44