TM 9-6115-660-13&Pa.b.c.d.e.2-44Disconnect the auxiliary fuel hose (4, figure 2-16) from the generator set external fuel supplyconnection (1). Elevate the free end of the auxiliary fuel hose to drain fuel back into theexternal fuel source (2). Place free end of auxiliary fuel hose on a clean surface.Disconnect auxiliary fuel hose (4) from fitting on container adapter (3).Store auxiliary fuel hose in the generator set storage compartment below the generator setcontrol panel, behind the bottom-right access door.Release the container adapter from the external fuel source by lifting the handle of the clamp(5). Remove the container adapter from the external fuel source. Close the external fuel sourceand load onto appropriate transportation.Store the container adapter in the accessory box.Figure 2-16. Disconnect Auxiliary Fuel (Typical).