TM 9-6115-658-13&P
2-19
Table 2-2. Operator Preventive Maintenance Checks and Services (continued)
ITEM
NO.
INTERVAL
LOCATION
PROCEDURE
NOT FULLY
MISSION
CAPABLE IF:
ITEM TO
CHECK/SERVICE
26
During
CONTROLS AND
INDICATORS
PANEL
Observe the following indicators and ensure
they are operating properly.
OIL PRESSURE 25-60 psi (172-414-kPa)
VOLTAGE 120-240 VAC
27
During
GROUND ROD
CABLE AND
CONNECTIONS
Inspect ground rod and cable for loose
connections, breaks, damage and
corrosion.
Cable is missing or
damaged.
28
After
HOUSING
a. Check door, panel, hinges, and clamping
catches for damaged, loose, or corroded
items.
b. Inspect air intake and exhaust grills for
debris.
Cannot secure
doors.
29
After
IDENTIFICATION
PLATES
Check to ensure identification plates are
secure.
30
After
SKID BASE
Inspect skid base for cracks and corrosion.
Skid base is
cracked or shows
signs of structural
damage.
The fuels used in this generator set are flammable. Do not smoke or use open
flame when performing maintenance. Flames and explosion can occur resulting in
severe personal injury or death.
31
After
ENGINE
ASSEMBLY
Check for loose, damaged, or missing
hardware.
32
After
FUEL SYSTEM
Inspect fuel system for leaks, and
Damaged, loose, or missing hardware.
Any fuel leaks, and
damaged, loose, or
missing parts.
33
After
FUEL FILTER/
WATER
SEPARATOR
a. Inspect fuel filter/water separator for
leaks, cracks, damage, improper mounting,
or missing parts.
b. Drain water from fuel filter/water separator.
Any fuel leaks.
WARNING