TM 9-6115-604-34NAVFAC P-8-633-34Table 12-3. Operational TestsTESTPARAMILSTD705TEST STANDARDSMETHOD10. Malfunction Indicator12-10Refer to paragraph 2-10(Annunciation)11. Instruments12-10Ammeter-1.5% plus transducer, plus CT.Voltmeter-1.5% plus transformerKWMeter-1.5% plus transformer plus CT.,plus potential transformerFrequency Meter 1.5%P.F. Meter 1.5% plus transducer, pluspotential transformerKVAR Meter 1.5% plus C.T and potentialtransformerRegulator Range 60 Hz 3750 to 4575 Vline to line; 50 Hz 3420 to 4180 Vline to line12. Oil pressure shutdown12-11515.1aWarning: 37 to 41 psiswitch OP1/OP2(255 to 283 kPa)Trip:28 to 32 psi(193 to 221 kPa)13. Coolant temperature switch12-12515.2aWarning: 206 to 210°FWT2(97 to 99°C)Trip:215 to 219°F(102to104°C)14. Coolant level switch12-13--Warning: 5.2 to 5.5 inchesS13IS14(132 to 140mm)Trip:7.0 to 7.3 inches(178 to 185 mm)Coolant level measured from top of fillerneck15. Low fuel level switch FL312-14155.5Refer to paragraph 1214.16. Speed Switch12-15505.2a2070 to 2250 rpmSS1/SS2/SS317. Circuit interrupter12-16512.1 cTrip: instantaneous at (short circuit)(short circuit)currents in excess of 300 amps18. Circuit interrupter12-17512.2Trip: 15 to 25 seconds (overload current) at 130% overload19. Circuit interrupter12-18512.3cTrip: overvoltage, 2 to 4 (overvoltage and (overvoltage and second at 234to 244 undervoltage) undervoltage) V; undervoltage, 2.5 to 5 second at161 to 171 V20. Reverse power protective12-19--Refer to paragraph 1219device21. Phase sequence (rotation)12-20507.1cL1, L2, and L322. Phase balance (voltage)12-21508.1c1% of rated line to neutral voltage, maximum23. Regulator range12-22511.1c60 Hz: 3750 to 4575 V50 Hz: 3420 to 4180 V12-8
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business