Table 12-3. Operational Tests
TEST
PARA
MILSTD705
TEST STANDARDS
METHOD
10. Malfunction Indicator
12-10
Refer to paragraph 2-10
(Annunciation)
11. Instruments
12-10
Ammeter-1.5% plus transducer, plus CT.
Voltmeter-1.5% plus transformer
KWMeter-1.5% plus transformer plus CT.,
plus potential transformer
Frequency Meter 1.5%
P.F. Meter 1.5% plus transducer, plus
potential transformer
KVAR Meter 1.5% plus C.T and potential
transformer
Regulator Range 60 Hz 3750 to 4575 V
line to line; 50 Hz 3420 to 4180 V
line to line
12. Oil pressure shutdown
12-11
515.1a
Warning: 37 to 41 psi
switch OP1/OP2
(255 to 283 kPa)
Trip:
28 to 32 psi
(193 to 221 kPa)
13. Coolant temperature switch
12-12
515.2a
Warning: 206 to 210°F
WT2
(97 to 99°C)
Trip:
215 to 219°F
(102to104°C)
14. Coolant level switch
12-13
--
Warning: 5.2 to 5.5 inches
S13IS14
(132 to 140mm)
Trip:
7.0 to 7.3 inches
(178 to 185 mm)
Coolant level measured from top of filler
neck
15. Low fuel level switch FL3
12-14
155.5
Refer to paragraph 1214.
16. Speed Switch
12-15
505.2a
2070 to 2250 rpm
SS1/SS2/SS3
17. Circuit interrupter
12-16
512.1 c
Trip: instantaneous at (short circuit)
(short circuit)
currents in excess of 300 amps
18. Circuit interrupter
12-17
512.2
Trip: 15 to 25 seconds (overload
current) at 130% overload
19. Circuit interrupter
12-18
512.3c
Trip: overvoltage, 2 to 4 (overvoltage
and (overvoltage and second at 234
to
244 undervoltage) undervoltage) V;
undervoltage, 2.5 to 5 second at
161 to 171 V
20. Reverse power protective
12-19
--
Refer to paragraph 1219
device
21. Phase sequence (rotation)
12-20
507.1c
L1, L2, and L3
22. Phase balance (voltage)
12-21
508.1c
1% of rated line to neutral voltage,
maximum
23. Regulator range
12-22
511.1c
60 Hz: 3750 to 4575 V
50 Hz: 3420 to 4180 V
12-8