TM 9-6115-604-34NAVFAC P-8-633-34c.Test. See Figure 5-33.(1)Pick up voltage test.(a)With switch open, apply 120 V ac power to terminals 5 and 6 at rear of K115.(b)Adjust potentiometer for voltmeter indication of zero V ac.(c)Close switch.(d)While observing voltmeter, adjust potentiometer to increase voltage until relay trips.(e)Verify relay trips at 20 i4 V ac.(2)Time voltage test.(a)With switch open, apply 120 V ac power as in step (1), above.(b)Adjust potentiometer for voltmeter indication of 24 V ac.(c)Set time totalizing timer to zero seconds.(d)Close switch S2.(e)Verify relay trips at 1 ±0.5 seconds by referring to timer.d.Repair. See Figure 5-32. Repair ground fault relay K115 by replacement of defective components.e.Install. See Figure 5-9.(1)Remove cover from ground fault relay K111 (67). If installed, by removing screw and captive washerassemblies (68).(2)Install ground fault relay K115 (67) in cabinet A door and secure with screws (66).(3)Install cover on ground fault relay Kl15 (67) by installing screw and captive washer assemblies (68).(4)Connect wiring as tagged and discard tags.5-38. SYNCHRO CHECK RELAY K116 (69, Figure 59).a.Inspect. See Figure 5-9.(1)Inspect synchro check relay K116 (69) for damage.(2)Check wire connections for security.b.Remove. See Figure 5-9.(1)Tag and disconnect wires from synchro check relay KI16 (69).(2)Remove synchro check relay Kl16 (69) by removing screw and captive washer assemblies (62).c.Test.(1)Connect synchro check relay K116 to 120 V ac, 50/60 Hz power source and multimeter set to RX1 scale asshown in Figure 5-34. Apply 120 V ac, 50 Hz, A phase, to terminals 1 and 2 of relay K 116.(2)Apply 120 V ac, B phase, to terminals 3 and 4.(3)The multimeter should indicate infinite ohms (contacts open). Voltages are not synchronized.(4)Repeat steps (1) and (2), above, with 120 V ac. 60 Hz, C phase, applied to terminals 3 and 4.(5)The multimeter should indicate infinite ohms (contacts open). Voltages are not synchronized.(6)Connect synchro check relay K116 to 120 V ac 50/60 Hz power source and multimeter set to RX1 scale asshown in Figure 5-34.(7)Apply parallel 120 V ac, A phase, to terminals 1 and 2, and terminals 3 and 4 of relay K 116.(8)The multimeter should indicate zero ohms (contact closure).5-80
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business