TM 9-6115-604-34NAVFAC P-8-633-345-5. GENERATOR G1 CLEANING AND INSPECTION.a.Whenever the generator is disassembled, the windings should be given a thorough inspection and the insulationcleaned, if necessary. The inspection should cover the condition of the windings and insulation, and theeffectiveness of the supporting ties as evidenced by rigidity of the coil end turns.WARNINGAdequate ventilation must be available to avoid fire, explosion, and healthhazards where solvents are used Avoid breathing solvent vapors Rubber glovesor other suitable protection for the hands should be used.WARNINGDry cleaning solvent, PD-680, type 11, or equivalent, Is flammable and moderatelytoxic to the skin, eyes, and respiratory tract. Assure adequate ventilation.CAUTIONCare must be taken not to get solvent on insulating varnishes or deterioration ofvarnish will occur.b.Safety type solvent, such as PD-680, Type 11, or equivalent, should be used. The flash point of any solventused should be greater than 1 000F (38"C).c.Solvent is usually required to remove accumulated soil containing oil or grease. A wet rag with solvent issuitable for wiping. Dry components thoroughly with moisture-free, low-pressure compressed air.WARNINGCompressed air used for cleaning or drying can create airborne particles that mayenter the eyes. Pressure shall not exceed 30 psi (207 kPa). Wearing of goggles Isrequired to avoid Injury to personnel.d.Cleaning with a dry cloth may be satisfactory when components are small, and the surfaces are accessible.Blowing dirt out with compressed air is usually effective particularly when the dirt has collected in places whichcannot be reached with a cloth. Use dean dry air at 30 psi (207 kPa).e.Dust and dirt may be removed by brushing with bristle brushes followed by vacuum deaning. Do not use wirebrushes. Vacuum deaning is an effective and desirable method of removing dust and dirt.f.Electrical components, after deaning, storing, or shipping must be dried before placing in operation if testsindicate that the insulation resistance is below a safe value. See approved drying procedures in paragraph 5-4.5-6. TESTING GENERATOR G1. The following tests are used to check minimum insulation resistance while thegenerator is installed on the generator set. This group of tests is performed using 5 k V dc and 500 V dc megohmmeters.Additional testing of the generator is accomplished by performing tests on the individual components.a.Main Stator.(1)Shut down the generator set completely in accordance with paragraph 2-5 of the Operator andOrganizational Maintenance Manual.(2)Open main disconnect switch S120 in accordance with the Operator and Organizational MaintenanceManual.WARNINGPlace load cables In the park position prior to grounding generator leads. Failureto do so may result In Injury to personnel.(3)Remove rear cabinet B access panel. Use grounding stick to discharge generator leadsT1, T2, and T3where they connect to bad circuit breaker CB1 01.5-2
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business