ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12CAUTIONDo not allow the starter motor to operate more than 30 seconds. Allow It to coolat least 2 minutes before deenergizing the motor. Overheating will damage themotor.(1 ) Connect the starter assembly, see figure 4-33.(2) Use power supply to obtain 20 V dc on the voltmeter.(3) Using RPM gage and ammeter, check starter motor speed. At a minimum current draw of 95 amperes rpmshould be at 5500 Motor speed at the maximum current draw of 120 amperes should be 7500 rpm(4) Connect the starter motor See figure 4-34.Figure 4-33. No Load Test CircuitFigure 4-34. Circuit For Checking Pinion ClearanceDo not touch exposed electrical connection when a source of power such asutility power or another generator set is connected to the load terminals. Death orinjury may result from failure to observe this warning.(5) Momentarily flash a jumper lead between terminals M and G. The dove will shift Into cranking position andremain so until the battery Is disconnected.(6) See Figure 4-35. Push on drive to eliminate slack.(7)Measure the distance between the pinion and the interior nose housing wall with a feeler gage. Distanceshould be within the 21/64 to 25/64 inch range.(8)Disconnect test set up.(9)Replace entire starter assembly if solenoid is bad.4-89