ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
Figure 3-13. Fuel Lines
g.
Maintenance of the Ether Injection Assembly. Refer to Figure 3-15.
Ether is highly flammable and toxic to the skin, eyes, and respiratory tract. Use
only In an adequately ventilated area. Skin, eye, and respiratory protection is
required to avoid injury to personnel.
(1) Inspect.
(a) Check tightness of ether start tank (1) in threaded mount of solenoid valve (2) It should be fully seated
prior to operation of the generator set.
(b) Check that the cylinder wing nut (15) is securely fastened.
(c) Inspect ether line tubes (4 and 5) for kinks, breakage, ruptures, or damage.
(d) Check entire routing of ether line tubes to both intake manifolds. Loop clamps shall be properly spaced
and fastened securely.
3-41