ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12Figure 3-13. Fuel Linesg.MaintenanceoftheEtherInjectionAssembly. Refer to Figure 3-15.Ether is highly flammable and toxic to the skin, eyes, and respiratory tract. Useonly In an adequately ventilated area. Skin, eye, and respiratory protection isrequired to avoid injury to personnel.(1) Inspect.(a) Check tightness of ether start tank (1) in threaded mount of solenoid valve (2) It should be fully seatedprior to operation of the generator set.(b) Check that the cylinder wing nut (15) is securely fastened.(c) Inspect ether line tubes (4 and 5) for kinks, breakage, ruptures, or damage.(d) Check entire routing of ether line tubes to both intake manifolds. Loop clamps shall be properly spacedand fastened securely.3-41