ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12Table 3-3. Operator Troubleshooting (Continued)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION10. LOAD CIRCUIT BREAKER CB101 FAILS TO CLOSE. (CONTINUED)Step 3.Check position of C8123Close If set to open.11. AC/DC LIGHTS NOT WORKING.Check for defective light bulbsReplace light bulbsSECTION V. OPERATOR MAINTENANCE INSTRUCTIONS3-8. GENERAL. The instructions In this section are provided to assist the operator In maintaining the generator set. Ifdefective components are noted during Inspection, perform the repair or replacement procedures listed in this section. Ifno repair or replacement procedure is shown in this section, then you are not authorized to perform that procedure andyou must report the defective component to the next higher level of maintenance.MAINTENANCE LOCKOUT switch must be set to the MAINTENANCEposition prior to performing any maintenance and reset to OPERATIONwhen maintenance is completed.3-9.MAINTENANCE OF HOUSING AND BASE ASSEMBLY . The generator set Is enclosed In an all weather housing(see Figure 1-1 and Figure 1-2). Refer to step a, below, for general maintenance Instructions Detailed Instructions forspecialized maintenance of the housing and base assembly are provided in steps b through h, below.Dry cleaning solvent P-D-680, Type II, is flammable and moderately toxicto the skin, eyes, and respiratory tract. Skin, eye, and respiratory tractprotection is required to avoid injury to personnel.aGeneral Maintenance General maintenance consists of Inspections and servicing Inspection of weatherproofequipment and components Is required at periodic intervals Inspect for discolorations, leaks, or paint cracks. Servicethe equipment by keeping it clean, free of grease, corrosion, rust, and deterioration. Use clean cloth, stiff brushes,and dry cleaning solvent P-D-680, Type II, or equivalent, as required Repaint in accordance with MIL-T-704bAccess Doors and Covers The generator set uses several access doors and covers Check that doors do not bind In their frames, that they swing easily on their hinges, and that they remain closed when latchedcHousing Panels Check the housing panels for corrosion, holes, scrapes, and/or dents Check sound insulation material in control room and between switchgear and generator compartment for any evident damage.d.Shutter Assemblies. See Figure 3-5. Inspect and service all shutter assemblies on a regular basis. Check that the shutter assemblies can be adjusted for optimum ventilation Ensure that the openings are not clogged with debris of any type. Verify that the formed metal portions (louvers) of the fixed position shutters are fully open.3-23
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business