Item
No.
1
2
3
ARMY TM 9-6115-464-12
AIR FORCE TO 35C2-3-445-1
NAVY NAVFAC P-8-624-12
Table 2-2. Operator Preventive Maintenance Checks and Services
Interval
Before
Before
Before
Location
Item to
Check\
Service
Generator Set
Batteries
Cooling System
Procedure
Visually inspect the generator set for fuel,
oil, hydraulic, and coolant leaks (para 328
through 3-30). Check for proper ground
connections (para 2-4d).
Visually inspect batteries for cracked or
broken cases, corrosion on terminal posts,
damaged or frayed cables and loose con-
nections. Check electrolyte level (para
34).
Check coolant level. Proper level is two
Not Mission
Capable If:
CIass Ill oil or any
fuel leakage is de-
ected during in-
spection or ground
cable missing or not
connected.
inches below the overflow pipe. Add cool-
ant as required.
2-37