ARMY TM 9-6115-464-12
AIR FORCE TO 35C2-3-445-1
NAVY NAVFAC P-8-624-12
(3) Assembly and Installation.
(a) On bases ( 45, Figure 4-38, sheet 1 of 3), screw on lamps (44), and install cover (43).
(b) Install panel light assemblies (42), and nut (41).
(c) Reconnect electrical leads to panel light assemblies.
n.
Control Cubicle Wiring Harness Assembly.
(1)
(2)
(3)
(4)
(5)
Removal.
(a)
(b)
(c)
(d)
(e)
(f)
Tag and disconnect electrical leads to control cubicle assembly.
Remove self-locking nut (46, Figure 4-38, sheet 1 of 3) and screw (47) to remove damp (48).
Remove self-locking nut (49) to remove clamp (50). Do not remove self-locking nut (51) and
screw (52) unless replacement is necessary.
Remove self-locking nut (53) and screw (54) to remove damp (55).
Remove self-locking nut (56) and screw (57) to remove damp (58).
Remove self-locking nut (59) and screws (60) to remove wiring harness assembly (61).
Cleaning and Inspection.
(a)
(b)
(c)
(d)
Clean wiring harness assembly with filtered compressed air and a soft bristle brush or wipe with
a clean, lint-free cloth lightly moistened with an approved solvent.
Visually inspect wiring harness connector for cracks, corrosion, bent or broken pins, and stripped
or damaged threads.
Inspect insulation for burns, chafing, and deterioration.
Check electrical leads for burned, bent, corroded, damaged or missing terminals.
Testing. Check continuity of individual wires with a multimeter or continuity light using figures FO-1
and FO-2 as a guide.
Do not use acid core solder on electrical wiring. See appropriate manual in
Appendix A for wiring installation practices. Equipment damage could result
if caution is not observed.
Repair. Replace damaged wires, terminals, and connector by unsoldering connections, installing replace-
ment parts and soldering connections.
NOTE
If more than 30 percent of the wires are damaged or have been repaired, replace
the wiring harness and forward it to high level maintenance for rebuilding.
Installation.
(a)
(b)
(c)
(d)
(e)
(f)
Install wiring harness assembly (61, Figure 4-38, sheet 1 of 3), screws (60), and self-locking
nut (59).
Install clamp (58), screw (57), and self-locking nut (56).
Install clamp (55), screw (54), and self-locking nut (53).
If removed, install screw (52) and self-locking nut (51). Install damp (50) and self-locking nut (49).
Install damp (48), screw (47), and self-locking nut (46).
Connect electrical leads to control cubicle assembly.
4-93