ARMY TM 9-6115-464-12AIR FORCE TO 35C2-3-445-1NAVY NAVFAC P-8-624-12Table 4-2. Unit Troubleshooting - ContinuedMALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION14. BATTERY CHARGING AMMETER SHOWS EXCESSIVE CHARGING AFTER PROLONGED OPERATION.Step 1.Step 2.Step 3.Step 4.Step 5.Improperly adjusted alternator.Adjust alternator (para 4-19).Defective batteries.Replace batteries (para 4-14).Defective alternator.Replace alternator (para 4-19).Short in charging circuit.Check charging circuit. Repair or replace shorted wiring.Defective battery charging ammeter.Replace battery charging ammeter (para 4-63).15. AC VOLTMETER DOES NOT INDICATE VOLTAGE.Step 1.Step 2.Step 3.Defective Volt-Amp transfer.Replace switch (para 4-63).Defective voltage adjust rheostat.Replace defective voltage adjust rheostat (para 4-63).Defective ac voltmeter.Replace ac voltmeter (para 4-63).16. AC VOLTMETER INDICATES VOLTAGE, BUT FREQUENCY METER IS OFF SCALE.Step 1.Step 2.Step 3.Engine speed too slow.Adjust frequency rheostat (Precise sets only) (para 2-6). Increase engine speed with manual speedcontrol (utility sets only) (para 2-6).Defective frequency meter.Replace frequency meter (para 4-63).Defective frequency transducer.Replace frequency transducer (para 4-63).4-15