TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Figure 2-3. External Power Box Assembly, Removal andInstallation (Sheet 2 of 2)(2)Secure all generator set electrical cables in vicinity of installation.(3)Locate external power box assembly and attach screws, washers, and nuts at bottom of unit to the skid base(see figure 2-3).(4)Attach screws, washers, and nuts securing unit to frame support upright (see figure 2-3).(5)Install control cable per paragraph 2-13 b.(6)Connect electrical connectors J27 through J31 (and J32, if equipped with a housing).(7)Thread heavy electrical cables through sleeves (on front) through unit, and connect to the reconnection boxand circuit breaker. Secure cable tiedowns, as required.(8)Attach screws, washers, and nuts securing unit to reconnection box and enclosure (see figure 2-3).2-11