Figure 17-4. Vibration Isolator (12 required)
the outlet positioned slightly higher than the inlet. The
inlet and outlet openings must be large enough to
provide the volume/time flow air necessitated by the
heat rejection rating of the generator set.
NOTE
Output cooling air ducting should
never be smaller than engine
radiator core. When radiator and
fan assembly remains mounted
with the generator set.
17-29. To determine the air needed to remove unit heat
rejection in the installation enclosure or room, use the
heat rejection factors from table 17-2 and the following
formula:
Q = H
Where:
1.08 T
Q = Air in cubic feet/minute
H = heat in BTU/HR to be removed
T = Permissible room temperature rise in
degrees F.
17-8