TM 5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Figure 17-4. Vibration Isolator (12 required)the outlet positioned slightly higher than the inlet. Theinlet and outlet openings must be large enough toprovide the volume/time flow air necessitated by theheat rejection rating of the generator set.NOTEOutput cooling air ducting shouldnever be smaller than engineradiator core. When radiator andfan assembly remains mountedwith the generator set.17-29. To determine the air needed to remove unit heatrejection in the installation enclosure or room, use theheat rejection factors from table 17-2 and the followingformula:Q =HWhere:1.08 TQ = Air in cubic feet/minuteH = heat in BTU/HR to be removedT = Permissible room temperature rise indegrees F.17-8