TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Table 1-3. Parameters AC-0% DroopTEST METHODCHARACTERISTICPARAMETERVALUEMIL-STUD-705Voltage CharacteristicsRegulation (%)2%608.1Steady-state-stability (variation)(bandwith %)Short term (30 seconds)1%608.1Long term (4 hours)2%608.2Transient performanceApplication of 50% of rated loadDip (%) - 60 Hz20%619.2Recovery (seconds)3 sec619.2Rejection of rated loadRise (%) - 60 Hz30%619.2Recovery (seconds)no spec619.2WaveformMaximum deviation factor (%)5%601.1Maximum individual harmonic (%)2%601.4Voltage unbalance with unbalance load (%)5%620.2(Note 1)Phase balance voltage (%)1%508.1Voltage adjustment range50 Hz (120/208 volts)190 to 213V50 Hz (240/416 volts)380 to 426V511.160 Hz (120/208 volts)197 to 250V60 Hz (240/416 volts)395 to 500V511.1Frequency CharacteristicsRegulation (%)0.25%608.1Steady-state-stability (variation)(bandwith %)Short term (30 seconds)0.5%608.1Long term (4 hours)1%608.2Transient performanceApplication of 50% of rated loadUndershoot (%)4%608.1Recovery (seconds)4 sec608.1Rejection of 50% of rated loadOvershoot (%)4%608.1Recovery (seconds)4 sec608.1Frequency adjustment range (Hz)50 Hz+5%511.260 Hz+4%511.2NOTE1. The generator set connected for three phase output and supplying a single phase, unity power factor loadconnected line-to-line, with no other load on the set. The load current to be 25 percent of the rated full loadcurrent of the set.1-15