TM 5-6115-593-12TO 35C2-3-463-1Table 5-3. Remote Control Module Troubleshooting(Organizational Level)-ContinuedMALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION10. EMERGENCY SHUT-DOWN SWITCH IS SET TO ON POSITION BUT GENERATOR SET DOES NOT SHUTDOWN.Set 24V DC CONTROL CIRCUIT BREAKER (on generator control panel) to OFF and, using a multimeter,check for continuity across the terminals of EMERGENCY SHUT DOWN switch S22 as it is toggled to eachposition.If switch does not read zero ohms in one switch position and infinite in the other it should bereplaced.11. START AID SWITCH IS SET TO ON BUT GENERATOR SET DOES NOT START.Set 24V DC CONTROL CIRCUIT BREAKER (on generator control panel) to OFF and, using a multimeter,check for continuity across the terminals of START AID switch S2 as it is toggled to each position.If switch does not read zero ohms in one switch position and infinite in the other it should bereplaced.5-10