TM 5-6115-593-12
TO 35C2-3-463-1
Figure 4-36. Generator and Reconnection Board
Section XXIV. MAINTENANCE OF ELECTRIC HYDRAULIC ACTUATOR
4-64.
GENERAL. The electric hydraulic actuator
(figure 4-37) is part of a governing system to control
generator set speed, independently, in parallel, or with
commercial power. It is mechanically coupled to the
engine and electrically controlled by a load sharing
circuit assembly.
a.
Inspection. Check all parts for wear, cracks,
nicks, and corrosion. Check the electrical
connector for cracks or damage and wiring
connections for breaks.
b.
Service. The electric hydraulic actuator has
a reservoir (sump) containing engine oil.
Refer to Lubrication Order, LO5-6115-593-
12 and table 3-1 for proper oil. The sump is
equipped with a dipstick. Check level and
add oil, if necessary. Drain by removing
drain plug.
4-96