T a b l e 4 - 2 . T r o u b l e s h o o t i n g ( C o n t)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
9. ENGINE SHUTS DOWN.
S t e p 1 . C h e c k o i l l e v e l ( p a r a g r a p h 4 - 5 1 ).
Add proper grade of oil.
S t e p 2 . C h e c k f o r r e s t r i c t e d a i r c o o l i n g s y s t e m ( p a r a g r a p h 4 - 4 1 ).
C l e a n r e s t r i c t i o n s f r o m s y s t e m .
S t e p 3 . C h e c k f o r o v e r l o a d o n g e n e r a t o r .
Keep generator load within set capability.
S t e p 4 . C h e c k l o w o i l p r e s s u r e s w i t c h ( p a r a g r a p h 4 - 3 1 ).
Replace a bad switch.
S t e p 5 . C h e c k t h e r m o o v e r h e a t s w i t c h ( p a r a g r a p h 4 - 1 7 c ) .
Replace a bad switch.
10. ENGINE VIBRATES.
Step 1. Engine mounts loose or bad (paragraph 4-52).
T i g h t e n m o u n t i n g o r r e p l a c e a s n e c e s s a r y.
Step 2. Check for loose blower wheel.
T i g h t e n b l o w e r w h e e l.
S t e p 3 . C h e c k v a l v e c l e a r a n c e ( p a r a g r a p h 4 - 4 6 ).
R e s e t v a l v e c l e a r a n c e.
11. LOW GENERATOR OUTPUT VOLTAGE (NO LOAD).
S t e p 1 . L o w e n g i n e s p e e d.
S e t e n g i n e s p e e d t o a c h i e v e n o - l o a d f r e q u e n c y ( p a r a g r a p h 1 - 1 0 . b . ).
Step 2. Check voltage adjust rheostat (R1) setting (paragraph 4-38).
Set rheostat (R1) for proper output voltage.
12. HIGH GENERATOR OUTPUT VOLTAGE (NO LOAD).
S t e p 1 . C h e c k v o l t a g e a d j u s t r h e o s t a t ( R 1 ) s e t t i n g ( p a r a g r a p h 4 - 3 8 ).
Set rheostat (R1) for proper output voltage.
13. AC CIRCUIT BREAKER (CB1) WILL NOT CLOSE.
S t e p 1 . C h e c k f o r s h o r t c i r c u i t l o a d .
R e m o v e s h o r t c i r c u i t .
Change
2
4-9