TM 5-6115-584-34
NAVFAC P-8-622-34
TO-35C2-3-456-2
Table 6-3. AC Output Control Box Wiring Harness (Cont)
Wire No.
X21A12
X22A16
X23A16
X28A16
X29A16
X30A16
X30B16
X30C16
X31A16
X31B16
X32A16
X33A
X34A
X34A
X36A
X37A
X38A
X39A
X40A
X47A
X48A
X49A
16
16
16
16
16
16
16
16
16
16
16
X76A16
X77A16
X31F16
Gauge
12
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
Marking
Color
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
black
(4) AC Voltmeter (M5) (18, figure 6-3). Tag and
disconnect two leads from meter. Remove three screws,
nuts, and lockwashers attaching meter to control panel and
remove meter.
d. Meters (replace).
(1) Frequency Meter (M3) ( 16, figure 6-3). Position
meter in control panel and attach with three screws, lock-
washers, and nuts. Connect the two electrical leads and
remove tags.
(2) Frequency Transducer (A3) (56, figure 6-3).
Position transducer to back of control cubicle and attach
with four screws (54) and nuts (55). Connect the four electri-
cal leads and remove tags.
(3) Percent Current Meter (M4) (17, figure 6-3).
Position meter on control panel and attach with three
screws, lockwashers and nuts. Attach the two electrical leads
and remove tags.
(4) AC Voltmeter (M5) (18, figure 6-3). Position
meter on control panel and attach with three screws, lock-
washers, and nuts. Attach the two electrical leads and
remove tags.
Length
in Inches
10
20
15.5
14
19.5
14
15
32
7
22
16
14.5
17
19
28
28
25
26
21
22
20.5
16
16
34
35
Terminal Lugs
MS25036-156,MS25036-156
MS25036-153
MS25036-153
MS25036-153, MS25036-153
MS25036-153
MS25036-153, MS25O36-107
MS25036-107, MS25036-108
MS25036-153, MS25036-107
MS25036-107, MS25036-153
MS25036-107
MS25036-153, MS25036-108
MS25036-153, MS25036-153
MS25036-153
MS25036-153
MS25036-153, MS25036-153
MS25036-153, MS25036-153
MS25036-153, MS25036-153
MS25036-153
MS25036-153
MS25036-107, MS25036-153
MS25036-107,MS25036-153
MS25036-107,MS25036-153
MS25036-153, MS25036-108
MS25036-153
MS25036-107, MS25036-153
6-5. GENERATOR SET WIRING HARNESS.
a.
Remove (see figure 6-2). Refer to figure 6-2 and
remove wiring harness at terminal boards and connectors.
On ASK equipped generators, refer to Operator and Organi-
zational Maintenance Manual and remove cover assembly.
b. Repair. Replace wires and terminals as needed. See
table 6-2.
c.
Install (see figure 6-2). Refer to figure 6-2 and install
wiring harness at terminal boards and connectors. On ASK
equipped generators, refer to the Operator and Organiza-
tional Maintenance Manual and install cover assembly.
6-6. VOLTAGE REGULATOR.
a.
Test, on Equipment.
(1) Operate set at rated load and adjust output
voltage as follows:
(a) Refer to figure 6-5 (or 6-5.1) and turn
adjustment screw on resistor R15 (or R16) counterclockwise
until voltage becomes unstable.
6-8
Change 7