TM 5-6115-584-34
N A V F A C
Table 2-2. Fabricated Tools and Equipment
Nomenclature
Reference No. orNSN
Material Required
Pump mounting fixture
O. 375 cold rolled steel
Fabrication
Instructions:
Fabricate fixture as shown below. Drill F (0.255 in. -0.262 in. ) depth thru countersink 60°
to
0.332 in. diameter. Tap 0.3125-18
depth
Two holes located within 0.005 in. of true
position.
Sketch or Diagram:
4
1.250
T
COLD ROLLED STEEL
DRILL F (0.255 - 0.262)
DEPTH THRU
60
TO 0.332 DIA.
TAP 0.3125-18
DEPTH THRU
2 HOLES LOCATED WITHIN 0.005 OF TRUE POSITION
2-2