TM 5-6115-584-12NAVFAC P-8-622-12TO-35C2-3-456-1TM-05682C-12Table 4-2. Troubleshooting (Cont)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION9. ENGINE SHUTS DOWN.Step 1. Check oil level (paragraph 4-51).Add proper grade of oil.Step 2. Check for restricted air cooling system (paragraph 4-41).Clean restrictions from system.Step 3. Check for overload on generator.Keep generator load within set capability.Step 4. Check low oil pressure switch (paragraph 4-31).Replace a bad switch.Step 5. Check thermo over heat switch (paragraph 4-17c).Replace a bad switch.10. ENGINE VIBRATES.Step 1. Engine mounts loose or bad (paragraph 4-52).Tighten mounting or replace as necessary.Step 2. Check for loose blower wheel.Tighten blower wheel.Step 3. Check valve clearance (paragraph 4-46).Reset valve clearance.11. LOW GENERATOR OUTPUT VOLTAGE (NO LOAD).Step 1. Low engine speed.Set engine speed to achieve 60 Hz at frequency meter (paragraph 2-4).Step 2. Check voltage adjust rheostat (R1) setting (paragraph 4-38).Set rheostat (R1) for proper output voltage.12. HIGH GENERATOR OUTPUT VOLTAGE (NO LOAD).Step 1. Check voltage adjust rheostat (R1) setting (paragraph 4-38).Set rheostat (R1) for proper output voltage.13. AC CIRCUIT BREAKER (CB1) WILL NOT CLOSE.Step 1. Check for short circuit load.Remove short circuit.4-9