Short circuit relay.
Table 1-1. Time Standards
TM-5-6115-545-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
1
2
3
4
5
6
7
8
9
10
p.
Thermal
Wall
Converter,
400
Hz
.
DOD drawing No. . . . . . 69-589-2.
volts . . . . . . . . . . . 100/130.
Current . . . . . . . . . . 1 ampere.
Elements . . . . . . . . .3.
Phase . . . . . . . . . .3.
Wire . . . . . . . . . ..4.
Output . . . . . . . . . .20 MV dc. open circuit.
Output circuit
resistance
. .4.97 ohms.
Watts per element . . . . .96.3.
q.
Alternator
.
(1)
Stator
coils
winding
data
50/60
Hz
.
Type . . . . . . . . . . . 3 phase.
No. of slots and COils . . . 84/84.
Turns per coil. . . . . . .4.
Coils per group . . . . . .7.
Conductor. . . . . . . . .6 of AWG 15.
Span . . . . . . . . . . . . . . .1-15 span.
(2) Rotor coils winding data 50/60 Hz.
Resistance
. . . . . . . .
Conductor . . . . . . . .
Turns per coil. . . . . . .
No. of poles and coils . . .
0.390 ohm at 25°C.
9 of AWG #16 (0.0508).
103.
4.
(3) Stator coils winding data 400 Hz.
Type . . . . . . . . . ..3 phase.
No. of slots and coils . . . 108/108.
No. of coils per group . . .36 groups of 2,
36 groups of 1,
Turns per coil . . . . . . . . .5.
Span . . . . . . . . . . . l-4.
Conductor. . . . . . . . . AWG 16 and AWG 17.
(4)
Exciter
stator winding data.
Type of winding . . . . . .
No. of slots and coils . . .
No. of coils per group . . .
Turns per coil. . . . . . .
Span . . . . . . . . . . .
Conductor . . . . . . . .
salient pole dc.
10 slots, 10 coils.
1.
196.
1-2.
1 of AWG #21 (0.0285).
1 of AWG #22 (0.0253).
(5) Rotor coils winding data 400 Hz.
No. of poles and coils . . .24.
Turns per coil. . . . . . .30.
Conductor. . . . . . . . .4 of AWG 15.
(6)
Exciter
rotor
winding
data
.
Type of winding . . . . . .3 phase.
No. of slots and coils . . .36 slots, 36 coils.
No. of coils per group . . .6 groups of 2, 24
groups of 1.
Turns per coil. . . . . . .3 for 60/50 Hz, 5 for
400 Hz.
Span . . . . . . . . . . . l-4.
Conductor. . . . . . . . . 5 of AWG #16 (0.0508)
60/50 Hz. 3 of AWG
#16 (0.0508) 400 Hz.
Insertion sequence . . . . . 211/112/111/121/111
and repeat.
r.
Engine
Repair
and
Replacement
Standards
.
Table 1-2 lists manufacturer’s sizes, tolerances,
and maximum allowable wear and clearances.
s.
Schematic
Wiring
Diagrams
.
Figures 1-1
through 1-15 show the schematic wiring diagrams
for the 50/60 Hz and 400 Hz engine
generator
sets,
as well as schematic and wiring diagrams for elec -
trical assemblies,
relay
boxes and kits.
t
.
Torque
Values.
(1) Table 1-3 lists specific
torque
values.
(2) All torque values are calculated for oil
lubricated threads. Increase this value by 10
percent when threads are not lubricated.
u
.
Unit
Function
Differences
.
The engine gener -
ator sets are provided in three configurations accord-
ing to class and mode of operation. The class desig-
nation of a unit is determined by its
frequency
and
voltage performance and the mode designation is
dependent upon the output
frequency
. Table 1-4
provides a quick reference for determining engine
generator
set classification and special component
complement required.
v.
Performance
Characteristics
.
The electrical
performance characteristics for Class 1 and Class 2
sets are provided in tables 1-5 and 1-6.
1-5