-KEY-
4.
LUBRICANTS.
The following is a list of
lubricants with the Military Symbols and applicable
NOTES.
Specification numbers.
1.
FOR OPERATION OF EQUIPMENT IN
OE/HDO
MIL-L-2104
PROTRACTED COLD TEMPERATURES BELOW-100
OEA
MIL-L-46167
F. (-230 C). Remove lubricants prescribed in the key
GAA
MIL.-G-10924
for temperatures above-10 F. (-230 C). Clean parts with
SOLVENT, dry-cleaning. Relubricate with lubricants
Copy of this Lubrication Order will remain with the equip-
specified in the key for temperatures below-100 F. (-230
ment at all times; instructions contained herein are
C)
mandatory.
2.
OIL FILTER. After installing new filter element,
BY ORDER OF THE SECRETARY OF THE ARMY:
fill crankcase, operate engine 5 minutes, check housing
for leaks, check crankcase oil level and bring to full
mark.
FRED C. WEYAND
3.
OIL CAN POINTS. Every 50 hours lubricate
General, United States Army
hinges,
latches, control linkages, and all exposed
Chief of Staff
adjusting threads with OE/HDO.
FOLD
FOLD
4.
OIL LEVEL GAGE. The oil level can be checked
OFFICIAL:
with engine running or stopped. The gage is stomped
on both sides to indicate two different oil level locations.
VERNE L. BOWERS
The engine running side is stamped ADD, FULL, and
RUNNING. The STOPPED side is stamped ADD, FULL
Major General, United States Army
and STOPPED. Make sure correct side is being read.
The Adjutant General
DISTRIBUTION: To be distributed in accordance with DA
Form 12-25D, (qty rpr block no 1073)
Operator
maintenance requirements for Generator Sets, Engine
Driven, 100 KW, 60 HZ Utility.
* U.S. GOVERNMENT PRINTING OFFICE: 1990 O - 261-867 (20036)