Figure 3-143. 400 Hz Generator Stator Winding Procedures (Sheet 3 of 3)
Figure 3-145. 400 Hz Generator Rotor Winding Procedures

TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
  332    333    334    335    336  337  338    339    340    341    342  
ARMY    TM    9-6115-464-34 AIR  FORCE  TO  35C2-3-445-2 NAVY   NAVFAC   P-8-624-34 3. 4. 5. 6. 7. 8. 9. 10. INTERPRET   DRAWING   PER   MlL-STD-100. STACK   LAMINATIONS,   FIND   NOS.   1   AND   2, ON   I.D.   UNDER   2.5   ±   10%   TONS. BRAZE   CAGE   ROD,   FIND   NO.   3,   TO LAMINATIONS,   FIND   NO.   1,   IN ACCORDANCE   WITH   MIL–B-7883.   TYPE   1, GRADE   B,   BRAZING   FLUX   SHALL   BE   IN ACCORDANCE   WITH   AWS   TYPE   3A. ONE   COIL   SPACER   SHALL   BE   USED   AT EACH   OF   EIGHT   PLACES. APPLY   4   LAYERS   OF   TAPE,   FIND   NO.   8,   TO SECURE    CABLE    STUDS. APPLY   2   1/2   LAYERS   OF   TAPE,   FIND   NO. 12,   TO   ROD,   FIND   NO.   4. VACUUM–PRESSURE   IMPREGNATE   IN ACCORDANCE   WITH   72–2487. CLEAN   CABLE   STUDS   AFTER IMPREGNATION. TORQUE   CAP   SCREWS,   FIND   NO.   5,   TO 17–FT–LB   ±   10%   WHILE   THE LAMINATIONS    ARE    UNDER    PRESSURE. GROUND    INSULATION:    GREATER    THAN 200   MEGOHMS. HIGH   POTENTIAL:   1500   VOLTS. Figure 3-144. 50/60 Hz Generator, Rewinding Procedures 3-303 1. 2.