TM 9-6115-668-13
4.35 BATTERY CHARGING ALTERNATOR V BELT MAINTENANCE.
This task covers:
a. Removal
b. Installation
INITIAL SETUP
Tools
Equipment Conditions
General Mechanics Tool Kitt
Reference
(item 2, appendix B)
Generator Set 150 kW shut
Automotive Fuel and Electrical System Repair, Tool Kit
down, paragraph 2.5.2
(item 3, appendix B)
Materials/Parts
V belt, Summer (KHD 02235258)
V belt, Winter (KHD 01162093)
REMOVAL
1.
Open flaps (1, 2 figure 4-38).
2.
Remove air leading duct (paragraph 4.17) when possible.
NOTE
V belts are a matched set. Always replace both belts.
3.
Loosen screw (3) from clamping bracket (4) of battery charging alternator (9).
4.
Loosen screw (8) on battery charging alternator bracket.
5. Loosen screw (5).
6.
Pivot battery charging alternator (9) upward toward engine block.
7.
Remove V belts (7).
INSTALLATION
CAUTION
For amblent temperatures 24.8° F (-4° C) to 86° F (+30° C), use sum-
mer V belt.
For ambient temperatures 23° F (-5° C) to -49° F (45° C), use winter
V belts.
New V belts must be no more than 15% longer or shorter than the
old belts.
Operate V belts for no more than 15 minutes, then retension (para-
graph 4.34).
4 - 8 4