TM 9-6115-668-13Table 4-3. Unit Preventive Maintenance Checks and Services for Generator Set 150 kW-continued.ItemItem to beNot Fully MissionNo.IntervalChecked or ServicedProcedureCapable if:81000Air Filter AssemblyClean or replace filter cartridge annu-If AIR FILTER lampHours/ally or when AIR FILTER lamp is on.is on.AnnualRefer to paragraph 4.29.91000Battery Set AssemblyCAUTIONBatteries will not holdHours/charge.AnnualDo not use a lead acid batterycharger to recharge conventional,gal battery, or damage to batterymay occur.Remove and clean battery set assem-bly. At temperatures below 32 °F(0 C) or if starting is difficult, checkbattery charge. Refer to the nexthigher level of maintenance. SeeTM 9-6150-200-14.101000Flame Glowplug SystemAt temperatures below 32 °F (0° C)Hours/or if starting is difficult, check opera-Annualtion of flame glowplug system. Referto paragraph 5.30.11Semi-EPP IIIPerform load bank procedures inannuallyaccordance with paragraph 5.53.121000ValvesRefer to paragraph 5.54Diesel engine runsHours/roughly with poor out-Annualput.131000Cooling Blower AssemblyRefer to paragraph 5.55hours/AnnualChange 4-19