TM 9-6115-662-13&P
WARNING
SHUT DOWN GENERATOR SETS
BEFORE PERFORMiNG tiTINUITY
CHECKS. FAILURE TO OBSERVE
THIS WARNING COULD RESULT hl
SEVERE PERSONAL INJURY OR
DEATH.
CHECK CONTINUITY OF THE FOLLOWING
WI FROM K1-A1 TO UNIT A GENERATOR SET L1
NOT OK
W2 FROM K1-B1 TO UNIT A GENERATOR SET L2
OK
W3 FROM K1-C1 TO UNIT A GENERATOR SET L3
W4 FROM SWITCH BOX ASSEMBLY LO TO UNIT A
GENERATOR SET LO
REPAIR OR REPLACE ELEC-
REFER TO TM 9-6115-644-24
TRICAL LEADS PARAGRAPH 5-10
AND REPAIR GENERATOR SET
Figure 5-2. Unit A Has No Input Power to K1.
5-5